- Home
- »
- Our Products
- »
- Testing Equipment
Testing Equipment
With thorough industrial knowledge, we are engaged in manufacturing and exporting a wide range of premium quality Testing Equipment. The offered range of testing equipment is manufactured by our expert professionals using high-grade raw material and components that are procured from the reliable vendors of the market. These testing equipment are widely demanded in the residential, industrial & commercial sectors and electrical & electronics industry. Following are the equipment, offered range comprises:
ZMIRT Insulation Resistance Tester
Product Brochure
| Measurement Range | 200M Ohm |
| Resistance Range | 0–200 MΩ |
| Display Type | Digital |
| Brand | Zeal |
| Model Name/Number | ZMIRT |
| Test Voltage | 500VDC |
| Metering | 3 and 1/2 digit, Digital V and Resistance meter |
| Accuracy | +-1.5% FS +-2dgt |
| Power | 230V AC,50 Hz |
| Ripple | Less than 0.1% rms |
| IR Measurement Range | 0 to 200M Ohm |
Secondary Injection Kit
Product Brochure
| Phase Type | Single Phase |
| Current Rating | 0-1, 2, 5, 10, 20A at 10V & 0-50, 100, 200A at 4V |
| Testing Method | Secondary Injection |
| Mounting Type | Bench |
| Brand | ZEAL |
| Accuracy | +/ - 1% |
| Frequency | 50Hz |
| Power | 230volts +/- 10% |
| Output Voltage Range | 0 to 250 volts AC at 2 A AC, 0 to 270 V DC at 1A DC, 50v at 2 Amps AC, 110V at 2 A AC |
| Output Current Range | 0-1, 2, 5, 10, 20A at 10V and 0-50, 100, 200A at 4V |
| Metering | 3 and 1/2 digit digital meter. |
| Timer Measurement | 0-9.999 and 0-99.99sec in 2 steps |
Make: ZEAL
Input: 230volts+/- 10%, single phase, 50Hz, AC Output(s): (a) Current Output (s) available one at a time Output Voltage Range:
1) Continuously variable 0 to 250 volts AC @ 2A AC
2) Continuously Variable 0 to 270 V DC @ 1A DC
3) Fixed voltages :50v at 2 Amps AC, 110V at 2A AC
Output Current Range:
1) 0-1, 2, 5, 10, 20A at 10V
2) 0-50, 100, 200A at 4V
Metering: 3½ digit digital meter.
Timer Measurement: 0-9.999 & 0-99.99sees. in 2 steps
Accuracy: +/- 1%ACDC High Voltage Measurement Probe
Product Brochure
| Measurement Mode | Direct using DMM |
| Measurement Type | AC+DC |
| Brand | ZEAL |
| Voltage Range | 0-100 kv |
| Accuracy | For DC up to 40 kV 2%, above 40 kV add 0.05%/kV and For AC up to 40 kV 2.5%, above 40kV , 0.08% kV |
| Model Name/Number | ZM100KHVMP |
| Range | 0-100 kV AC & DC |
| Input Impedance | Greater than 220 MOhm |
| Attenuation Ratio | 1kV 100mV |
| Parameter | Specification |
|---|---|
| Model | ZM100KHVP |
| Voltage Range | 0 to 100 kV AC / DC |
| Attenuation Ratio | 1 kV : 100 mV |
| Input Impedance | > 220 MΩ |
| Accuracy (DC) | ±2% up to 40 kV+0.05% per kV above 40 kV |
| Accuracy (AC) | ±2.5% up to 40 kV+0.08% per kV above 40 kV |
| Mounting Box Dimensions | 200 mm (W) × 200 mm (D) × 100 mm (H) |
| Probe Length – Part 1 | 652 mm |
| Probe Length – Part 2 | 623 mm |
| HV Corona Ball | 133 mm |
| Total Length | 1408 mm |
| Weight (Unit only) | Approx. 3 kg |
| Weight (with Case) | Approx. 12 kg |
| Additional Features | Measures AC & DC HV with DMMSeparate ground clipHigh attenuation & accuracySupplied with carrying case |
Insulation Resistance Tester
Product Brochure
| Measurement Type | Insulation |
| Measurement Range | 20G Ohm |
| Resistance Range | Up to 20G Ohm |
| Power Consumption | 230V AC, 50 Hz |
| Resolution | 3 and 1/2 digits. |
| Display | 3.5 Digit |
| Brand | ZEAL |
| Model Name/Number | ZMIRT5k |
| Display Type | Digital LED Display |
| Insulation Resistance Ranges | 2GOhm, 20GOhm (Range selection by Toggle switch) |
| Test Voltage | 500V, 1000V, 2500V, and 5000V(Voltage range selection by Rotary switch) |
| Accuracy for Test Voltage | +- 1.0 % of Reading +-5 digits |
| Accuracy for Resistance | +- 1.5 % of FS +- 3 digits |
Make: Zeal Model: ZMIRT5k Power: 230V AC, 50 Hz
Insulation Resistance ranges: 0.2GΩ, 2GΩ, 20GΩ
Range selection by Rotary switch
Test Voltage: 0.5 kV, 1kV, 2.50kV, and 5kV Test Voltage Range selection by Rotary switch Resolution: 3½ digits.
Accuracy for Test Voltage: ± 1.0 % of Reading ± 5 digits
Accuracy for Resistance: ± 1.5 % of Rdg ±3 digitsHigh Voltage Breakdown Testers
Product Brochure
| Test Type | HV Breakdown Tester |
| Voltage Range | 5 kV |
| Operation Type | Manual |
| Usage/Application | Industrial |
| Power Supply | 230 V AC, +/- 10% , 50/60 Hz |
| Brand | Zeal |
| Programmable Timer | 0 to 999 second |
| Accuracy | For kV 1.5% FS, for mA 1.5% |
Customers can avail from us a comprehensive range of High Voltage Breakdown Testers. These high voltage breakdown testers are manufactured by our team of expert professionals using the excellent quality raw material in compliance with the industry laid standards norms. Offered testers are easy safe to handle and user-friendly.
Features of High Voltage Breakdown Testers:
- Audio and visual alarm when HV on and off
- Test on and off switch to start and interrupt test
- Precise trip current setting
- Inbuilt timer
- Press to set switch for leakage current setting
General Specifications:
Type | Maximum Test Voltage (kV) | Typical Leakage currents (mA) |
AC HV Tester | 5, 10, 80 | 20, 30, 100, 350 |
DC HV Tester | 5, 10, 40 | 20, 30, 100, 350 |
AC/DC HV Tester | 5, 10, 20 | 20, 100, 350 |
AC DC High Voltage Breakdown Testers
Product Brochure
| Test Type | HV Breakdown Tester |
| Voltage Range | 5 kV |
| Operation Type | Manual |
| Voltage | (DC) 0 to 5000 V continuously variable by multi turn potentiometer |
| Brand | Zeal |
| Tripping Current | Adjustable 1.0 to 30.0 mA by press to set switch and potentiometer on mA meter |
| Tripping Current optional | Test Voltage and leakage current programmable by external 0 to 10 V DC |
| Accuracy class of Test Voltage | +- 0.1% +- 2 least count |
| Accuracy of leakage Current | +- 0.5% +- 2 least count |
| Display Digital | Voltage 4 and 1/2 digit , Current 3 and 1/2 digit |
| LED Power Supply | 230V+-10%, single phase, 50Hz |
AC DC High Voltage Breakdown Testers is designed to meet the expectation of user at economy without compromise with performance. It will find application in Industries, Test Laboratories, R D Organization and Service Industries.
Specifications:
- Automatic Timer:
1 to 999-second Settable by thumb wheel switches on 7 segments 3 digit display With timer ON/OFF switch
- Indication for Pass/Fail:
Audio (Buzzer) and visual (Neon) alarms when HV is ON, Output Trips when a breakdown occurs i.e. leakage exceeds than set current. Test FAIL indicated by LED If device under test successfully handles the test voltage for the set time duration then Test PASS indicated by LED
Ground Continuity Tester
Product Brochure
| Test Type | Short Test, Open Circuit Test, Continuity Test |
| Indication | LED |
| Power Source | Mains |
| Model Name/Number | ZMGCT |
| Brand | Zeal |
| Accuracy | V 1.5% of reading, A 1.5% of reading, mOhm 1.5% of reading +- 5 dgt |
| Open Circuit Voltage | 8V |
| Resistance Measurement Range | 0 to 200 milli Ohm |
| Test Current | 30 A AC |
| Programmable Timer | 1 to 60 sec |
| Metering | 3 1/2 digit Digital V, A and milli Ohm meter |
| Indications | Trip, Test On, Test Off |
Acceptable setting: By press to set switch & potentiometer, using digital milli Ohm meter
Three Phase Secondary Injection Test Kit
Product Brochure
| Number Of Channels | 1 |
| Current Rating | 50A |
| Phase Configuration | Single Phase & Three Phase |
| Operation Mode | Manual |
| Country of Origin | Made in India |
| Input | 220 Volt AC,50Hz |
| Output Voltage Range | 0 to 300 V (L-N) or 0 to 520 Phase to Phase |
| Output Current Range | 0 to 50 A per phase |
| Mode | 3 Phase, 4 Wire |
| Output ports | Vr ,Vy, Vb - N, Ir (Hi, Lo),Iy (Hi, Lo),Ib (Hi, Lo) |
| PF Range | 0.5 to Unity |
| Compliance | 20 VA, at FS on V ranges, Compliance: 150 VA, at FS on A channels |
| Frequency | 45 to 60 Hz |
| Setting | By coarse and fine set of potentiometer for Voltage and Current By push button keys. |
| Metering | Digital AC Voltmeter, Digital AC Ammeter, Universal meter to indicate PF, W, VA, Var of each phase. |
| Accuracy | Class 0.15% (for V, A, W and Whr ) |
| Sinusoidal Outputs | THD 1.5% |
| Protections | Overload and Short circuit |
Make: ZEAL, Model: ZM3ΦSIK Input: 230 Volt AC,50Hz
Output Voltage Range: 0 to 300 V (L-N) or 0 to 520 Phase to Phase
Output Current Range: 0 to 6 A per phase
Mode: 3 Phase, 4 Wire
Output ports: Vr, Vy, Vb – N, Ir (Hi, Lo), Iy (Hi, Lo), Ib (Hi, Lo)
PF Range: 0.5 to Unity
Compliance: 20 VA, at FS on V ranges, Compliance: 30 VA, at FS on A channels
Frequency: 45 to 60 Hz
Setting: By coarse and fine set of potentiometer for Voltage and Current By push button keys.
Metering: Digital AC Voltmeter, Digital AC Ammeter, Universal meter to indicate PF, W, VA, Var of each phase. Also average of all phases, WHr Programmable current display to accommodate any CT ratio.
Accuracy: Class 0.15% (for V, A, W and WHr) Sinusoidal Outputs: THD 1.5% Protections: Overload and Short circuit.